Fire Service Act Occupancy Classification: Category 15 (Offices)

Under Item 1 of the Fire Service Act Enforcement Order, "Category 15" covers "Offices, Banks, and Similar Workplaces"[cite: 27].

Unlike "Specified Fire Prevention Objects" with high public traffic (e.g., restaurants in Category 3, hotels in Category 5, retail stores in Category 4), Category 15 classifies as a "Non-Specified Fire Prevention Object" because it primarily accommodates regular employees, resulting in relatively relaxed fire system requirements[cite: 27].

Target Facilities Included in Category 15

Primary Fire Protection Requirements for Category 15 Standalone Facilities

Installation requirements for core fire protection equipment are triggered by building gross floor area and floor levels[cite: 27]:

Equipment Type Primary Installation Thresholds for Category 15 (Offices)
Fire Extinguishers Gross floor area ≥300 m² (lowered to ≥50 m² for basement, windowless, or 3rd+ floor areas)[cite: 27]
Automatic Fire Alarm Systems Gross floor area ≥1,000 m² (lowered to ≥300 m² for basement, windowless, or 3rd+ floor areas)[cite: 27]
Indoor Fire Hydrants Gross floor area ≥700 m² to 3,000 m² (varies depending on structural fire resistance and interior finish)[cite: 27]
Fire Sprinkler Systems Mandated for 11th floor and above, or basement areas with total floor area ≥2,000 m²[cite: 27]
Exit & Directional Signs Mandated for basements, windowless floors, and 11th+ floors (standard ground floors allow basic signage)[cite: 27]
Emergency Alarm Appliances/Systems Mandated for facilities with maximum occupant capacity ≥50 persons[cite: 27]

Key Compliance Considerations for Office Real Estate Operations

  1. Conversion to Mixed-Use Buildings (Category 16-A) via Retail/Dining Tenants:
    If a single restaurant (Category 3) or retail store (Category 4) moves into a building previously occupied solely by Category 15 offices, the entire building is reclassified as a "Mixed-Use Specified Fire Prevention Object" (Category 16-A)[cite: 27]. This reclassification frequently forces retroactive, expensive fire alarm system upgrades building-wide[cite: 27].
  2. Office Partitioning & Layout Renovation Risks:
    Constructing new enclosed rooms (conference rooms, executive suites) during office renovations creates unmonitored dead zones beneath ceiling fire sensors or sprinklers, mandating sensor relocation or auxiliary head additions[cite: 27].