Logistics Facility Planning & Improvement | Related Knowledge Menu

jp tw Email MAP___ By Logistics Technology Research Institute
Supplementary Legal Guide

Use Classification "Item 13 (Factories, Workplaces, Maintenance Shops, Movie Studios)" in the Order for Enforcement of the Fire Service Act

"Item 13" in Appended Table 1 of the Order for Enforcement of the Fire Service Act is a use classification that mainly refers to factories, workplaces, maintenance shops, movie studios, etc.

Like Item 14 (Warehouses) and Item 15 (Offices), it is classified as a "non-specified fire prevention property" where there are few unspecified general users. However, because the fire risk is more likely to increase due to the nature of the work, the handling of hazardous materials, open flames, and mechanical equipment, specific fire equipment standards are established for it.

Classification of Item 13 (A / B)

Item 13 is subdivided into two categories, "A" and "B," depending on the handling of hazardous materials and the level of fire risk.

Classification Target Facilities Characteristics & Risks
Item 13-A Automobile repair shops, movie/TV studios, and workplaces with high fire risk Facilities handling hazardous materials and combustibles such as gasoline and paint, with a relatively high risk of ignition
Item 13-B General manufacturing factories, printing factories, sewing factories, and workplaces (other than A above) Facilities where general product manufacturing, processing, and assembly work take place

Main Installation Standards for Fire Protection Equipment under Item 13

The standards vary depending on the building's structure (whether it is a fireproof structure) and the work environment, but the main guidelines are as follows:

Equipment Name Main Installation Mandatory Line in Item 13 (Factories/Workplaces)
Fire Extinguisher Total area of 150㎡ or more (Basements, windowless floors, and 3rd floors and above: floor area of 50㎡ or more)
Automatic Fire Alarm System Total area of 500㎡ or more (May be 300㎡ or more in cases like automobile maintenance shops under Item 13-A)
Indoor Fire Hydrant System Total area of 700㎡ to 1,400㎡ or more (Varies depending on structure and fire resistance performance)
Sprinkler System In principle, floors on the 11th story or above, or under specific requirements such as when an automated rack warehouse is attached
Outdoor Fire Hydrant System Total floor area of 1st and 2nd floors is 3,000㎡ or more (9,000㎡ or more for fireproof structures, etc.)

Relationship with Logistics Facilities and Warehouses (Item 14)

In logistics hubs and distribution centers, if there are areas performing not just cargo storage but "packing work," "labeling," or "simple assembly/processing," the following determinations may be made during fire inspections or prior consultations:

← 4-2. Return to the main text of Fire Service Act / Energy Conservation Act To Menu List